Flexfiller Standard 250D Twin Pump Floor Standing FC FILL 250D 17398

SKU
115430
£2,096.29
-
+
 
Overview

Flexfiller 250D Twin Pump

  • Cabinet: Mild steel CR4. Float:
  • WRAS Approved Torbeck Side Entry.
  • Break Tank: WRAS Approved Polypropylene.
  • Pump: PEDROLLO / ULKA (Unit dependant. See pump details for more information).
  • Connection: Brass / Polypropylene.
  • Pipework: Braided flexihose / EPDM.
  • Finish: Powder coated.
  • Suitable for membrane pressure expansion tank
  • Suitable for compressor-controlled automatic expansion unit
  • Outer pipe diameter 1 return [mm] 21.3
  • Pressure [bar] 1 - 5
  • Height [mm] 800
  • Width [mm] 470
  • Depth [mm] 320
Type Dimensions
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
F
[mm]
H
[mm]
K
[mm]
M
[mm]
Flexfiller 125D - 280D 470 320 800 500 150 800 225 550 590
Flexfiller 2160D 600 390 800 500 150 800 225 550 590

Flexfiller Standard 250D Twin Pump Floor Standing FC FILL 250D 17398

Flexfiller 250D Twin Pump

Compact and totally enclosed digital pressurisation units with electronic pressure transducer and user-friendly microprocessor for use on sealed system in order to provide a minimum system pressure requirement.
Available in single or twin pump configuration.

The Flexfiller is a floor standing, high flow rate (<18 l/min) top-up pressurisation unit with 18 litre break tank.

Application:

  • Commercial.
  • Industrial.
  • Residential.


System Volume (Guide): < 300,000 litres.

  • For system volumes up to 300,000 litres.
  • Break Tank: 18 litre break tank with type
  • AB Air Gap Fluid Cat 5.
  • MODBUS Communication output.
  • System quick-fill mode.
  • Password protection for parameter entry.
  • Pressure settings in 0.1 bar increments.
  • Service reminder option (12 months).
  • Pump pulse option (2 second pulse if inactive for 60 days).
  • Flood protection options. High flow applications (<18.0 l/min).
  • Event logging for pump start, individual pump run hours counter, electrical interruption and common alarm.
  • Volt free contacts for common fault, high pressure, low pressure, pump fault, pressure transducer fault.
  • Electric pump, 230V 50Hz 1ph (110V 60Hz 1ph available upon request).
  • Colour: Black (RAL 9005).
More Information
Delivery Next Business Day
EAN Code 08712874173989

Flexfiller 125D

Operating Conditions:

  • Maximum system temperature: 85 ºC.
  • Maximum ambient temperature: 40 ºC.
  • Relative humidity 95% non-condensing.
  • Noise Rating Data: < 75 dBA.

Certifications and Standards Applied:

  • PED 2014/68/EU Sound Engineering Practice.
  • IEE - Electrical Safety Guidance.
  • EMC 2004/108/EC. BS 7074 Parts 1 to 3.
  • Machinery Directive 95/16/EC.
  • Electronic Components have been tested and comply with the EMC Directives.
  • EN 61000-6-2: Generic Standards – Immunity standard for industrial environments.
  • EN 61000-6-3: Generic Standards – Emission standard for residential, commercial and light industrial environment.
  • CE marked components, where applicable.
  • WRAS approved float valve to BS1212.
  • IP54 (BS EN60529) rated controller.
Type

Pump

quantity

Connections Max.
Delivery
Pressure 
[bar]
Power
Consumption
[kW]
Full Load
Current
[A]
Weight
[kg]
Order 
Code
System
[mm]
Mains
Supply
[mm]
Overflow
[mm]
Flexfiller 125D 2 15 (12" M) 15 (12" M) 22  2.5 2 x 0.50 39 1 17395

Type Dimensions
A
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
F
[mm]
H
[mm]
K
[mm]
M
[mm]
Flexfiller 125D - 280D 470 320 800 500 150 800 225 550 590
Flexfiller 2160D 600 390 800 500 150 800 225 550 590